Verify if the client setup is correct for the Hitachi Vantara CCI Engine.
Before You Begin
Ensure that you set the user privileges and the command device properties.
Procedure
-
With the command device to test raidcom commands, create a horcm instance.
-
Start the horcm instance.
If the instance fails to start, read the horcm logs.
-
After the horcm instance started successfully, type the following commands:
raidcom -login –IMinst_no -s serial
raidcom lock resource -resource_name meta_resource –IM<inst no> -s <serial>
raidcom unlock resource -resource_name meta_resource –IM<inst no> -s <serial>
where:
-
Inst_no is the horcm instance number.
-
Serial is the array’s serial number.
If any of the above commands fails, read the horcm logs.
-
-
For Windows systems, type the following command:
raidscan –x findcmddev 1-100
If the command device is within the range, then the command returns a valid command device for the array.